Why a whole row powers down on purpose - and why that is revenue, not a fault.
A whole row going dark during grid stress is usually the site selling its power back, not a fault. Curtailment = the site drops load on command to earn money or dodge a charge.
Big sites run demand-response contracts. When the grid is short, they cut load and collect. In August 2023 Riot was paid $31.7M to power down over 95% of its load during a Texas heat wave.
| Bucket | Amount | What for |
|---|---|---|
| Economic/power curtailment | ~$24.2M | Sold power back / stopped during high prices |
| Demand-response credits | ~$7.4M | Paid to be on-call to drop load |
| Total | $31.7M | One month (Aug 2023); Riot's rounded figures |
ERCOT sets a site's transmission charges for the NEXT year from its own load during summer's four highest 15-minute grid-wide peaks - the Four Coincident Peaks (4CP).
Two different reasons a machine slows or stops. Do not confuse them.
| Term | What happens | Why |
|---|---|---|
| Curtail | Stop or near-zero watts | Grid event / demand response |
| Throttle | Reduced hashrate or speed | Usually thermal or a power cap |